DB-PX5 - PowerVisa 440® / PowerGuide® 4400 / PowerXplorer® PX5 Op. Skills
© 2006-2010 by PowerCET Corporation. All rights reserved. (100616)
50
©2006-2008 PowerCET Corporation. All rights reserved.
99
Event data is measured in compliance
with the criteria set by IEEE 1159 or
IEC 61000-4-30 Class A
Press: None (Raw Data) if you do not
want to characterize event data
according to any measurement
standard—uses less CPU time.
Press: IEEE 1159 Standard (typical
for North America) or IEC 61000-4-30
Standard to characterize event data
Press: OK to accept changes in
characterizer setting and return to
Advanced Options menu
Wizard Setup: Characterizer Options
©2006-2008 PowerCET Corporation. All rights reserved.
100
Periodic readings of power
parameters are stored as
trend data in a journal
Statistical info is captured
regardless of limit settings,
even when no
disturbances occur
Press: Journal Limit
Wizard Setup: Journal Limit