5-7
CH 5/ Start Menu
Monitoring
modes
(continued)
Long-term Timed Recording, Demand, Energy
: Performing a statistically valid power
quality energy survey requires the capture of a set of basic data over an extended period
of time. PX5 is designed to facilitate long-term monitoring by collecting min/max/avg
data at each predetermined interval in order to perform post-process harmonic and
other events analysis. PX5 is also designed to be left unattended in the field, recording
statistically representative data for long-term analysis. Using the Dranetz
lockable
portable case option or other available enclosures, power quality studies can be carried
out in harsh weather environments.
Continuous Data Logging, Demand, Energy
: This logs the rms and power values once
per second for totally gapless logging. Cyclic triggers are disabled. No waveforms are
recorded under this monitoring mode.
EN50160 Power Quality
: EN50160 monitors and reports Quality of Supply (QOS)
compliance as specified by the EN standard. The seven parameters required by
EN50160 to determine QOS compliance are: Power Frequency, Supply Voltage
Variations, Rapid Voltage Changes, Supply Voltage Unbalance, Harmonic Voltage,
Interharmonic Voltage, and Mains Signalling. A full discussion on EN50160 is found
on Chapter 8 Reports.
Motor Quality
: Automatically sets up the parameters that affect the operation of
motors. Motor parameters include True Power Factor, Horsepower, and Derating
Factor, among others. This setup mode is available in PX5 firmware V2.0 and higher.
In this section
The following topics are covered in this section.
Topic See Page
Current Probe Selection 5-8
Scale Factor Setup 5-10
Circuit Type Selection 5-12
Nominal Values 5-14
Mode of Operation 5-17
Monitoring Mode 5-18
Advanced Options 5-19
Site Name/Memory Card 5-20